Service and technical support for our clients:

ASGE-60BI-3

  • Cooling capacity 16,0 kW
  • Heating capacity 17,0 kW
  • 3-year warranty
  • DC Inverter technology
  • Autorestart function
  • Anticorrosion treatment of exchangers
  • SCMI-01.4 slave unit (control by 0–10 V)
  • SCMI-01.4 communication module is separate product
CapacityCooling / Heating16,0 / 17,0kW
Power SupplyInto Outdoor Unit380 – 415 / 3 / 50V / Ph / Hz
Power InputCooling / Heating5,45 / 5,40kW
Rated Power InputCooling / Heating5,95kW
Power CurrentCooling / Heating7,7 / 7,6A
Rated Power CurrentCooling / Heating9,0A
Air FlowOutdoor Unit6600m3 / h
Sound Pressure Level at 1 mOutdoor Unit57dB(A)
Sound Power LevelOutdoor unit72dB(A)
Refrigerant / Charge / Eq. CO2R32 / 3,60 / 2,43type / kg / t
Additional Refrigerant40g / m
Refrigerant Liquid PipeDiameter3/8 / 9,5inch / mm
Refrigerant Gas PipeDiameter5/8 / 15,9inch / mm
Max pipe length without additional refrigerant7,5m
Maximum overall length of piping75m
Max. Elevation30m
Dimension (w x h x d)Outdoor Unit900 × 1345 × 412mm
Package (w x h x d)Outdoor Unit1033 × 1395 × 443mm
Net / Gross WeightOutdoor Unit112,0 / 122,0kg
Package volumeOutdoor unit0,638m3
Operating Temperature RangeCooling– 20 ~ 48°C
Operating Temperature RangeHeating– 20 ~ 24°C
 
Notes

The specification of products is subject to change based on further development of the units by the producer and can be changed without prior notice. Refer to rating label.
R32 (single component refrigerant HFC), GWP of refrigerant used: 675.
Contains fluorinated greenhouse gases covered by the Kyoto Protocol.

COMMUNICATION MODULE SCMI-01.4

Question about the Product
Name